|
Ample Power Smart Charger Manager (SCM)
Installation and Operating Instructions
Model SCM-12 November 9, 2011
Figure 1 - SCM-12 Wiring Diagram
Ample Power Smart Charger System II
The Ample Power Smart Charger System II consists of a Smart Charge
Manager (SCM), one to four Power Supply Chargers (PSC), and one isolator
for each PSC. Other miscellaneous options may also be added such as:
a shunt for current limiting, a remote alarm, remote switches, or
a parallel solenoid.
Mounting the SCM
The SCM is protected against ambient humidity, but must be mounted
in a dry location free of moisture, dust and other environmental
insults. The SCM will operate in temperatures to 60 C
(140 F).
WARNING: Do not mount the Power Supply Charger(s) or
isolator(s) in a closed compartment. Provide adequate ventilation
for cooling. Do not place objects around the Power Supply Charger(s)
or isolator(s) that will obstruct air circulation.
Wiring Diagram
The wiring diagram above is the only way to wire the
SCM. Do not wire in any other way, such as combining ground
wires or battery positive wires. For safety purposes, always use fuses where
shown.
Blocking Diode not needed with the PSC55-12 units.
The blocking diode shown in the wiring diagram is not used with the
PSC55-12 Power Supply/Charger. Wire the positive charger lug directly to
positive distribution.
Signal Names and Functions
All voltages are given for 12-volt SCMs. Double the voltages
given for 24-volt models. There are three terminal blocks on
the SCM, TB1, a sixteen-pin block, TB2, a six-pin block and TB3, a
four-pin terminal block. TB3 is reserved for future use. Refer to
Figure 1 for locations of TB1, TB2, TB3, S1, and S2.
- , (required) ...the positive power input for the SCM.
- , (optional) ...positive input, necessary if parallel solenoid is used.
- , (required) ...battery voltage sense wire input.
- , (required) ...ground return and reference for SCM.
- , (recommended) ...ground for temperature sensor.
- , (recommended) ...positive wire of temperature sensor. Voltage at is 2.98V at @
25
C (77 F), and varies plus and minus with temperature at
the rate of 0.01V per degree C. Some battery manufacturers require temperature
sensing of the battery for warranty purposes. Under all cases except for
temporary troubleshooting, we recommend using the temperature sensor at all
times.
- , (optional) ...an output signal that is activated to ground when energizing the parallel solenoid. The maximum load is 1.5 Amps.
- , (optional) ...a positive true input signal that holds the SCM in the absorption state.
- , (required) ...the regulation control output signal for the first Power Supply/Charger module.
- , (optional) ...sense wire input from charger side of shunt.
- , (optional) ...sense wire input from ground side of shunt.
- , (optional) ...the regulation control output signal for the second Power Supply/Charger module.
- , (optional) ...the regulation control output signal for the third Power Supply/Charger module.
- , (optional) ...the regulation control output signal for the fourth Power Supply/Charger module.
- , (optional) ...a positive true input signal that activates current limiting set-point #1.
- , (optional) ...a positive true input signal that activates current limiting set-point #2.
- , (optional) ...5 Volt supply for remote alarm options only.
- , (optional) ...a positive true signal that locks the SCM at the gas set-point.
- , (optional) ...a ground true signal conveying status information, (green LED).
- , (optional) ...a ground true signal conveying error information, (red LED).
- , (optional) ...current limiting value from 0-5 Volts corresponding to 0-0.05 Volts (full scale) of current shunt.
- , (optional) ...panel ground return.
- , (reserved) ...future use.
- , (reserved) ...future use.
- , (reserved) ...future use.
- , (reserved) ...future use.
Configuring the SCM
The SCM is configured by setting two internal dip-switches
as explained in the following section. Remove the cover to proceed.
DIP Switches
There are two dip-switches, , and on the printed circuit board,
as shown in Figure 2 below.
Figure 2 - DIP Switches
The dip-switches are used to select a charge profile appropriate for the
batteries in the system and the settings for three current limits.
First, select a charge profile by setting the first three battery type
switches on S1 according to the following table.
Table 1. - Battery Selector Switches
Current Limiting
Current limiting is used to prevent excess demand from the AC source, for
example when running the chargers from a shore connection with only 15
Amps of AC available. With an optional control panel and shunt, current
limit can be set manually at any time.
In addition to the remote panel current limit
potentiometer option, the SCM provides a means to activate current limiting
whenever selected AC appliances are operated. These might be the water
heater or air conditioner. To activate current limit automatically when a
given appliance is consuming AC power, auxiliary relays are required.
Signals on and are used to activate current limiting which
is set on switches and . As shown in Figure 2 there are three
limit settings, , , and . is activated when
is positive. Likewise, is activated when is positive. When
both and are activated, is chosen instead of
or .
Each limit setting uses four dip switches as shown in .
is set on switches on .
is set by switches on .
is set on switches on .
The switches set the amount of current permitted as a percentage of full scale on the optional
shunt used to measure current. Full scale is defined as 0.05 Volts, or
50 millivolts. Table 2 shows the switch settings available for the desired amps percentage.
Table 2. - Current Limit Selector Switches
State Indicator
The green State Indicator shows the charging state of the SCM.
Status is shown by flashing the green Status Indicator with On and Off time in seconds
as shown in Table 3 below.
Table 3 - Green State Indicator
| Status |
On |
Off |
| Bulk Charge |
2 |
1 |
| Gas Charge |
6 |
1 |
| ABS Charge |
1 |
1 |
| Float Charge |
2 |
2 |
| Locked |
3 |
1 |
| ABS Hold |
1 |
3 |
- Bulk Charge - During bulk charge, the power supply is operating at
its current limit. Battery voltage depends on state of charge, but will
be less than the float voltage.
- Float Charge - Float charge is done at a voltage chosen to maintain
a full charge, not deliver any significant current to the battery. The
float status will be displayed briefly after the bulk charge status during
the time that the microcomputer analyzes the charge process.
- Gas Charge - This charge is done at the voltage where the
electrolyte is just starting to decompose into hydrogen and oxygen. This
status is observed only briefly as voltage climbs to the absorption
set-point.
- Absorption Charge - The voltage is held at the absorption voltage
and continues for a time dependent on battery chemistry.
- Lock - A signal is provided that permits the SCM to be locked at the
gassing voltage ...13.8 Volts for most liquid electrolyte batteries.
- ABS Hold - A signal is provided that holds the SCM at the absorption
voltage. This signal is typically used with the Energy Monitor/Controller
to hold the SCM in absorption until the monitor recognizes the battery
full conditions as programmed by the user.
Error Indicator
Abnormal conditions are reported via the red Error Indicator.
Errors are identified by On and Off times of
the Red Error Indicator as shown in Table 4 below.
If the red Error Indicator is continuously
illuminated, the SCM is operating improperly and requires troubleshooting.
Table 4 - Red Error LED
| Error |
On |
Off |
| B1 Volts Disconnected |
3 |
1 |
| Over Temperature |
3 |
3 |
| Faulty Temperature Sensor |
6 |
6 |
| Voltage Runaway |
6 |
3 |
B1 Volts disconnected indicates that the signal on TB2-3 is missing.
Over temperature error occurs at 130 F, (54 C).
A temperature sensor is declared faulty if readings obtained are
abnormal. This error can also be exhibited if the temperature
sensor is wired in reverse.
Voltage runaway can be caused by the Power Supply/Charger module(s)
ignoring the SCM or from other charge sources that are not controlled by the SCM.
Troubleshooting
First, look at the section above and
make sure that all required wires are in place and properly connected.
We have found that moving a wire such
as or a few feet away from a good
Battery Positive or Negative Distribution could result in
undesirable regulation due to voltage spikes in the system.
To help diagnose voltage set-points, remove the
connection to disable temperature compensation and prevent a faulty temperature
sensor from affecting the system.
Second, if the problem still exists, obtain a copy of the SCM
Troubleshooting Guide which is available from the following sources:
Ample Power Service Center
- Web: http://www.amplepower.com/trouble/
- E-mail: support@amplepower.com
- Phone: (206) 789-4743 or Fax: (206) 789-9003
The troubleshooting guide was designed to help isolate a majority of the
installation problems. Fill out the Troubleshooting Guide to determine if
all measurements meet the specified requirements.
Finally, if you are unable to remedy the problem, contact the
service center with the SCM Troubleshooting Guide completed for
referencing.
Advanced Application Information
Automating Current Limits
Figure 3 shows how an AC relay can be connected to a water heater circuit
to automatically activate a programmed current limit whenever the water
heater is turned on. This can prevent main or shoreside breakers from
being overloaded by excessive demand. This circuit is useful for small
generators as well.
Figure 3 - Automating Current Limit Example
This circuit should only be wired by a certified electrician who
understands all applicable codes for proper AC wiring. Be sure that
relays rated for AC are used. Ample Power dealers sell relays that are
appropriate for this application, and include details about relay
terminals.
Note the 12-Volts lamp on the signal going to TB1. The lamp assures that
the relay contacts conduct enough current to `wipe' the contacts clean of
surface films. Such films may not breakdown on the low current draw of
the current limit inputs to the SCM.
Activating Current Limit Three
Figure 4 shows how a single relay can be used to activate current limit 3
which requires that both TB1-15 and TB1-16 are driven positive.
Any small signal diode such as a 1N4001 is appropriate.
Figure 4 - Automating Current Limit 3 Example
Refer to Figure 3 for wiring that is not shown in Figure 4.
Packing Power Supply/Chargers
Figure 5 shows how to pack power supply/chargers modules in
parallel for increased amperage output capability.
Note
that the modules are connected in parallel with each module
connecting to one of the control lines on the SCM.
Figure 5 - Packing Power Supply/Chargers
Stacking Power Supply/Chargers
Power Supply/Charger modules can be stacked to provide 24-Volt
charging. A stacking interface module is used.
Information about stacking is provided below.
Interface to Energy Monitor/Controller
The SCM interfaces to the Energy Monitor/Controller using the ABS signal,
TB1-8. This interface operates exactly as that of the Next Step
Regulator. Installation drawings for the Energy Monitor/Controller show
the ABS control signal. That signal can be connected to both the Next
Step Regulator and the SCM.
Power Supply/Charger Power Requirements
Table 5, below, shows: the apparent power requirement in watts;
the power factor, PF; and the recomended AC service amperage rating
per unit operated over the full AC input voltage range (90 - 140 VAC).
NOTE: The power requirements can be reduced by using the current limit
feature of the SCM.
Table 5 - Power Supply Charger AC Line Power Requirements
| Model |
Watts (Power Factor) |
AC Service |
| PSC15-12 |
375 W (0.7 PF) |
5 A |
| PSC30-12 |
750 W (0.7 PF) |
10 A |
| PSC45-12 |
1100 W (0.7 PF) |
15 A |
| PSC55-12 |
1400 W (0.7 PF) |
20 A |
Smart Charger Manager 24V Supplement (SCM-24)
Installation and Operating Instructions
Model SCM-24 November 9, 2011
Figure 1 - SCM-24 Wiring Diagram
Supplement
This supplement includes additional information specific to the 24 Volt version
of the Smart Charge Manager (SCM-24).
Ample Power Smart Charger System II 24V
The Ample Power Smart Charger System II 24V consists of one SCM-24,
one SCM-24 Balancer Module, two to eight Power Supply Chargers (PSC), and one isolator
for each PSC. Other miscellaneous options may also be added such as:
a shunt for current limiting, a remote alarm, remote switches, or
a parallel solenoid.
Mounting the SCM Balancer Module
The SCM Balancer Module is protected against ambient humidity, but must be mounted
in a dry location free of moisture, dust and other environmental
insults. It will operate in temperatures to 60 C
(140 F).
24V Wiring Diagram
For proper operation of the SCM-24, wire it as shown in Figure 1.
Do not wire it in any other way, such as combining ground
wires or battery positive wires. For safety purposes, always use fuses where
shown.
Signal Names and Functions
As shown in Figure 1, there is one 7-pin terminal blocks for the SCM Balancer Module
- , (required) ...24V battery voltage sense wire input.
- , (required) ...12V battery voltage sense wire input.
- , (required) ...ground return and reference for the SCM Balancer Module.
- , (required) ...the regulation control output signal for the fisrt Power Supply/Charger module on the 24V side.
- , (optional) ......the regulation control output signal for the second Power Supply/Charger module on the 24V side.
- , (optional) ......the regulation control output signal for the third Power Supply/Charger module on the 24V side.
- , (optional) ......the regulation control output signal for the fourth Power Supply/Charger module on the 24V side.
Stacking and Packing Power Supply Chargers
Figure 2 shows how to stack and pack power supply chargers modules in
series-parallel for increased amperage output capability in 24V systems.
Note that the modules are first connected in parallel.
Each power supply/charger module
on the lower 12V side connects to one of the control lines on the SCM-24.
Each power supply/charger module
on the upper 12V side connects to one of the control lines on the SCM-24 Balancer.
The lower 12V and upper 12V banks are then connected in series for 24V.
Figure 2 - Stacking and Packing Power Supply Chargers
|