|
Smart Alternator Regulator V3
Installation and Operating Instructions
Ample Power Models SARV3-12P and SARV3-24P October 12, 2011
Mounting the Regulator
The regulator is protected against ambient humidity, but must be mounted
in a dry location free of moisture, dust, and other environmental
insults. The regulator will operate in temperatures to 60 C
(140 F).
Wiring Diagram
The wiring diagram above is the only way to wire the Smart
Regulator. Do not wire it in any other way, such as combining ground
wires or battery positive wires. For safety purposes, always use fuses where
shown.
NOTE: For those familiar with earlier regulators such as the SAR-V2 or Next
Step Regulators, note that all inputs and outputs on the SAR-V3 are active
on a positive signal. That means the solenoid, the
and the are wired to their
respective devices with the other end of the device returned to Negative
Distribution. All inputs at the terminal block are activated when they
are connected to battery voltage. Leave unused optional terminals
unconnected.
Signal Names and Functions
Battery voltage set-points are specified for
each voltage system, 12 or 24 volts, as 12 / 24 volts, respectively.
- , (optional) ...an output that has
a positive voltage when the regulator detects that the house battery is
being charged. The maximum load is 1.5 Amps.
- , (required) ...an input that
that turns the alternator field circuits of the regulator on when battery
voltage is applied. Typically it is connected to the ignition switch.
Typical draw is 0.003 Amps.
NOTE: On gasoline engines DO NOT connect at the spark coil ...
connect at the ignition switch.
- , (required - connect this wire
first) ...the reference ground for the regulator. All battery voltages
are referenced to this connection.
- , (required) ...the power input
source for the alternator field current, , , and . Amperage draw on this wire is rated at
15 Amps maximum. To completely deactivate the regulator, a suitable switch
(not shown) can be inserted into this line.
- , (required) ...an output that
is driven positive by the regulator to make the alternator charge. Voltage
at this point depends on how much current the alternator should produce and
varies from zero to battery voltage.
- , (required) ...the return line
for field current.
NOTE: Do not jumper this wire to the tab.
- , (optional) ...an input, when connected
to battery voltage, that locks the regulator set-point at the battery
gassing voltage. Used to prevent higher voltages when halogen lights are used.
Refer to the section for the operating description.
- , (required) ...the sense wire
for battery voltage. Any erroneous voltage drop in this wire from the battery
can cause overcharge.
- , (recommended) ...ground side of
the temperature sensor, which is supplied with the regulator.
- , (recommended) ...positive side
of the temperature sensor. Voltage at is 2.98V at @
25
C (77 F), and varies plus and minus with temperature at
the rate of 0.01V per degree C. Some battery manufacturers require temperature
sensing of the battery for warranty purposes. Under all cases except for
temporary troubleshooting, we recommend using the temperature sensor at all
times.
- , (optional) ...a positive voltage
applied at will lock the regulator at the absorption set-point.
This is typically used with the Ample Power Energy Monitor/Controller.
Refer to the section for the operating description.
- , (optional) ...an output that
has a positive voltage blink rate identical to the red . Refer to the Error Indicator section. Maximum current permitted
from this output is 0.05 Amps.
- , (optional) ...an output that
has a positive voltage blink rate identical to the green . Refer to the Status Indicator section. Maximum current permitted
from this output is 0.05 Amps.
- , (optional) ...an input that
activates the regulator's duty-cycle current limiting when battery voltage
is applied to this connection. This duty-cycle current limit is adjusted with
potentiometer R11 (Refer to Figure 2). Refer to the section for the operating description.
- , (optional) ...an input that
activates either the regulator's equalization mode or a second
duty-cycle current limit, depending on the internal jumper .
This input is activated when battery voltage is applied to .
The duty-cycle current limit is adjusted with potentiometer R12 (Refer to
Figure 2). Refer to the section for the operating
description.
Figure 2. Internal Settings Locations
Status Indicator
The green Status Indicator and the external , if wired,
shows the charging state of the regulator. Status is shown by flashing the green
Status Indicator with On and Off times in seconds as shown in Table 1 below.
Table 1. Green Status Indicator
| Status |
On |
Off |
| ON/OFF Input Off |
3 |
3 |
| Bulk Charge |
2 |
1 |
| Gas Charge |
6 |
1 |
| Absorption Charge |
1 |
1 |
| Step to Float |
1 |
6 |
| Float Charge |
2 |
2 |
| Gas Lock |
3 |
1 |
| ABS Hold |
1 |
3 |
| Equalization Charge |
6 |
6 |
Error Indicator
The red Error Indicator and the external , if wired,
reports abnormal conditions. Errors are identified by On and Off times of
the red Error Indicator as shown in Table 2 below. They are listed in the
order that errors are displayed if there are multiple errors. All errors,
except the last one, attempt to shut off the field drivers until the error
condition subsides.
Note: The last error can also be a warning that voltage getting to the
regulator on the input is insufficient to fully drive
the field output.
Table 2. Red Error Indicator
| Error |
On |
Off |
| Voltage Runaway |
6 |
3 |
| Field Short Circuit |
3 |
6 |
| Bat. Volts disconnected |
3 |
1 |
| Can't turn field off |
1 |
1 |
| Bad Temperature Sensor |
6 |
6 |
| Over Temperature |
3 |
3 |
| Can't turn field on |
1 |
3 |
| Missing GROUND connection |
6 |
0.5 |
Voltage and Absorption Time Set-points
The voltage and the time of the absorption cycle are controlled by the internal
dip-switch, S1. Refer to Figure 2 for the location of S1. Select a charge
profile by setting the battery type switches on S1 according to the following
table.
Table 3. Battery Type Selection
| Battery Type |
Sw 1 |
Sw 2 |
Sw 3 |
| Thick Plate Liquid |
Off |
Off |
Off |
| Medium Plate Liquid |
On |
Off |
Off |
| East Penn Gel |
Off |
On |
Off |
| Concorde AGM |
On |
On |
Off |
| Optima |
Off |
Off |
On |
| Exide Gel |
On |
Off |
On |
| Johnson Control Gel |
Off |
On |
On |
| Ample Power Gel |
On |
On |
On |
What You Should See
The regulator is on whenever power is present at . Without
voltage at the input, the regulator is simply controlling
the parallel solenoid, and will close the solenoid whenever the voltage on
indicates that the main battery is being charged.
When the regulator is first turned on via , the red Error
Indicator will glow for 5 - 8 seconds before extinguishing. Then the green
Status Indicator will then start to flash the charge status.
If there is a positive voltage on the input, then the
alternator should start to charge after the red Error Indicator goes off.
Thus, alternator charging can be controlled via the input.
ABS Input
When battery voltage is applied to this input, the regulator is held at the
absorption set-point. Removal of the input signal causes the regulator to
begin stepping toward the float voltage. Step-to-float is an intermediate
mode where the float set-point is approached in small steps over time.
This is done in an attempt to maintain some alternator output and thus keep
the tachometer alive.
LOCK Input
This input locks the regulator at the gassing set-point, which is half-way
between the absorption and float set-points.
Removal of the signal toggles
between stepping to float, or going to the absorption set-point.
The first activation and then removal of the signal causes
the regulator to step float. The next activation and then removal of the
signal causes the regulator go to the absorption set-point,
initializing the absorption timer. This cyclic behavior repeats. Thus, the
LOCK input can be used to completely control the charge state at float, gas
or absorption.
Input Priorities
The signal overrides the signal.
The overrides the
and signals.
On the current release, the signal overrides the
signal. The signal will limit current with
either or .
Current Limiting
Two 20-turn potentiometers with two input signals permit duty cycle current
limiting at two independent set-points. Duty cycle current limiting is a mode
where the percentage-of-time that the regulator is driving the field is
set by the potentiometer. Current limiting is useful to reduce alternator
output, and thus reduce horsepower requirements from the engine.
Two settings are available. The control inputs are , and
.
Note that the input serves a dual function depending on
whether an internal jumper, , is in place. See the section for more information.
For normal limiting on a small engine, assert the input.
The input can be connected to the same switch that enables
another load on the engine. For example, a clutch driven pump may require
a further reduction in current, so wire the input to the
switch that activates the clutch for the water pump. The potentiometer for
is R11. R12 sets the current limit for the
input. Refer to Figure 2 for R11 and R12 locations.
NOTE: The input is used here as a second current limit
set-point. See the following section below for information to do equalization.
Equalization
Equalization is a process where the voltage on the battery is allowed to rise
to a higher voltage, typically 16.2 / 32.4 Volts for most batteries, where the
applied current is limited to 3 - 7% of the Ah capacity of the
battery. The applied current must be set using R12.
The input is used for a second current limit whenever the input
signal is activated.
To enter the actual equalization mode, the two pins of must be
first shorted with a jumper terminal or a switch connected to the two pins,
refer to Figure 2. This changes the mode of the input signal
to regulate at the equalization voltage set-points as well as current limit.
Then the input should be momentarily activated for at least
two seconds and then released. A second momentary action will terminate the
equalization process.
Equalization will terminate automatically whenever the ending voltage or
time is achieved.
CAUTION: Equalization produces a higher voltage than some normal
equipment can tolerate. Turn off equipment that will not tolerate an input
of 17 / 34 Volts or more.
NOTE: The Smart Regulator does not permit equalization for the gel batteries but does
permit equalization of absorbed glass matte batteries at an appropriate voltage.
Alternator Requirements
The alternator must be an externally regulated model with one
brush connected to ground and the other brush fitted with a
connection to make the field connection, (P-type).
NOTE: Alternators not rated for continuous operation
at high current and temperature may fail when driven by the
regulator unless current is limited to a safe value.
Troubleshooting
First, look at the section above and
make sure that all required wires are in place and properly connected. We
have found that moving a wire such
as or a few feet away from a good
Battery Positive or Negative Distribution could result in
undesirable regulation due to voltage spikes in the system.
To help diagnose voltage set-points, remove the
connection to disable temperature compensation and prevent a faulty temperature
sensor from affecting the system.
NOTE: With temperature sensing, a higher battery temperature will result in
a lower battery voltage. Likewise, a lower battery temperature will
result in a higher battery voltage.
Second, if the problem still exists, obtain a copy of the SAR V3
Troubleshooting Guide which is available from
http://www.amplepower.com/trouble/index.html.
The troubleshooting guide was designed to help isolate a majority of the
installation problems. Fill out the Troubleshooting Guide to determine if
all measurements meet the specified requirements.
Support
Support
for the
Smart Alternator Regulator is available at:
http://www.amplepower.com/phpBB3.
|