Most installations that fail to operate from the start are due to some wiring problem or an incompatible alternator. Read the ERROR INDICATOR section below to determine if the regulator identified an error. Then proceed to the Troubleshooting Steps section to isolate and remedy the problem. If the problem cannot be remedied, consult technical support via email:
support@amplepower.com.An
ERROR INDICATOR is provided that indicates errors that have been detected by the regulator. Errors are indicated by flash codes ...so many seconds on and so many seconds off. Under normal conditions, the ERROR INDICATOR is off. Seven abnormal conditions are reported by flashing the light at various rates as shown in Table 1, below.Table 1 ERROR INDICATOR Codes
| Error | On Time (sec) | Off Time (sec) |
| Voltage Runaway | 6 | 3 |
| Field Short Circuit Detect | 3 | 6 |
| No Battery Sense | 3 | 1 |
| Cannot Turn Off Field Output | 1 | 1 |
| Battery Over Temperature | 3 | 3 |
| Abnormal Temperature Sensor | 6 | 6 |
| Cannot Turn On Field Output | 1 | 3 |
| Missing GROUND connection | 6 | 0.5 |
F |
NOTE: The ERROR INDICATOR comes on when the regulator is first powered up. This tests the LAMP to verify that the ERROR INDICATOR, error lamps and/or alarms operate. |
Description of ERROR INDICATOR Codes
Battery Voltage Runaway: The voltage runaway condition is raised when the battery voltage exceeds (by » 0.5 volt) the desired voltage determined by the regulator. The
ERROR INDICATOR will turn on for 6 seconds and off for 3 seconds. This can be caused by other charger sources that do not follow the regulators charge sequence (such as shore power battery chargers), in which case it is best to turn the other charge sources off while the regulator is running.Field Short Circuit Detect: When the regulator detects the field current going out of the FIELD terminal exceeds the factory value, the regulator signals the error condition. The regulator will attempt to power down the FIELD terminal and repeatedly attempt to restore power to the FIELD terminal. Activation of this error may indicate a partially shorted field winding within the alternator.
No Battery Sense: When the regulator does not sense the battery voltage, it can not regulate. After a short delay, the regulator will shut down and display an error code of 3 seconds on and 1 second off.
Cannot Turn Off the Field Output: When the regulator cannot turn off the field output, the alternator charges at its maximum rate. Obviously, this can destroy batteries if not corrected. The signal for this condition is easy to determine since it is 1 second on and 1 second off. There are two causes for this error: one, a shorted driver in the regulator, that is, the driver no longer goes off when commanded; and two, the
FLD wire is not connected to the alternators Field, which is more likely to be the case.Abnormal Temperature Sensor: This condition will shut down the regulator indicated by an error code of 6 seconds on and 6 seconds off. There are two possible causes for this: one, a shorted or reverse wired temperature sensor; or two, a temperature less than -103° F / -75° C detected.
Battery Over Temperature: If temperature sensing is utilized, an over temperature condition may arise if the battery temperature should exceed 140° F/60° C, signaled by an error code of 3 seconds on and 3 seconds off. In this case, the regulator will shut down after a short delay period.
Cannot Turn On the Field Output: When the regulator cannot turn on the field output, it turns off the output drivers and delays for about one minute before attempting to regulate again. It will display an error code of 1 second on and 3 seconds off. The regulator will repeat this procedure indefinitely. There are three main causes for this: one, if there is no power supplied to the power input (
B+); two, if the alternator field is shorted to ground; and three, if the field wire is shorted to ground by rubbing through insulation or loosening from the field terminal. The engine should be shut off and the problem solved.Missing
GROUND connection: This error can occur when the GROUND connection is missing or poor.
First, Take some measurements.
Fill in Table 2 completely. Fill in Column A first, Column B second, and Column C last. These measurements can catch 99% of all wiring errors if done meticulously. Leave the o checkbox empty until you have gone through the analysis in Table 3.
Table 2 Your Voltage Measurements.
Column A |
Column B |
Column C |
|||
Connected? |
Ignition Off |
Ignition On & Engine is not Running |
Ignition On & Engine is Running |
||
Row 1 |
PARALLEL Terminal |
o |
o |
o |
|
Row 2 |
ON/OFF Terminal |
o |
o |
o |
|
Row 3 |
GROUND Terminal |
o |
o |
o |
|
Row 4 |
B+ Terminal |
o |
o |
o |
|
Row 5 |
FIELD Terminal |
o |
o |
o |
|
Row 6 |
ALT.GND Terminal |
o |
o |
o |
|
Row 7 |
LOCK Terminal |
o |
o |
o |
|
Row 8 |
BAT.VOLTS Terminal |
o |
o |
o |
|
Row 9 |
T- (BLK) Terminal |
o |
o |
o |
|
Row 10 |
T+ (RED) Terminal |
o |
o |
o |
|
Row 11 |
ABS Terminal |
o |
o |
o |
|
Row 12 |
ERROR LAMP Terminal |
o |
o |
o |
|
Row 13 |
STATUS LAMP Terminal |
o |
o |
o |
|
Row 14 |
LIMIT Terminal |
o |
o |
o |
|
Row 15 |
EQL Terminal |
o |
o |
o |
|
Row 16 |
House Battery + |
o |
o |
o |
Second, Analyze the Results.
Table 3, below, contains general information about valid results. Refer to the sub-sections following the table for the descriptions of problems. Check the valid values here in Table 3 against your measurements in Table 2. Place a þ check in the box provided if the value is valid.
Table 3 Valid Voltage Measurements.
Column A |
Column B |
Column C |
||
Ignition Off |
Ignition On & Engine is not Running |
Ignition On & Engine is Running |
||
Row 1 |
PARALLEL |
0.00V if de-activated. Up to 0.5 V less than Row 4, Col. A if activated. |
0.00V if de-activated. Up to 0.5 V less than Row 4, Col. B if activated. |
0.00V if de-activated. Up to 0.5 V less than Row 4, Col. C if activated. |
Row 2 |
ON/OFF |
0.00 V |
Same value as Row 16, Col. B and up to 35 V |
Same value as Row 16, Col. C and up to 35 V |
Row 3 |
GROUND |
0.00 V |
0.00 V to +0.05 V |
0.00 V to +0.05 V |
Row 4 |
B+ |
Same value as Row 16, Col. A |
Same value as Row 16, Col. B |
Same value as Row 16, Col. C |
Row 5 |
FIELD |
0.00 V |
Up to 1.5 V less than Row 16, Col. B |
Anywhere between 0.00 V and a little less than Row 16, Col. C. |
Row 6 |
ALT.GND |
0.00 V |
0.00 V ± 0.05 V |
0.00 V ± 0.05 V |
Row 7 |
LOCK |
Activated: Battery Voltage Not Activated: 0.00 V |
Activated: Battery Voltage Not Activated: 0.00 V |
Activated: Battery Voltage Not Activated: 0.00 V |
Row 8 |
BAT.VOLTS |
Same value as Row 16, Col. A |
Same value as Row 16, Col. B |
Same value as Row 16, Col. C |
Row 9 |
T- (BLK) |
Same value as Row 3, Col. A |
Same value as Row 3, Col. B |
Same value as Row 3, Col. C |
Row 10 |
T+ (RED) |
0.00 V |
Sensor Connected: 2.98 V @ 77° F / 25° C ± 0.01V for every ± 1.8° F / 1° C Sensor Not Connected: 4.7 V ± 0.2 V |
Sensor Connected: 2.98 V @ 77° F / 25° C ± 0.01V for every ± 1.8° F / 1° C Sensor Not Connected: 4.7 V ± 0.2 V |
Row 11 |
ABS |
Activated: Battery Voltage Not Activated: Same value as Row 3, Col. A |
Activated: Battery Voltage Not Activated: Same value as Row 3, Col. B |
Activated: Battery Voltage Not Activated: Same value as Row 3, Col. B |
Row 12 |
ERROR LAMP |
0.00V if de-activated. Up to 0.5 V less than Row 4, Col. A if activated. |
0.00V if de-activated. Up to 0.5 V less than Row 4, Col. B if activated. |
0.00V if de-activated. Up to 0.5 V less than Row 4, Col. C if activated. |
Row 13 |
STATUS LAMP |
0.00V if de-activated. Up to 0.5 V less than Row 4, Col. A if activated. |
0.00V if de-activated. Up to 0.5 V less than Row 4, Col. B if activated. |
0.00V if de-activated. Up to 0.5 V less than Row 4, Col. C if activated. |
Row 14 |
LIMIT |
Activated: Battery Voltage Not Activated: Same value as Row 3, Col. A |
Activated: Battery Voltage Not Activated: Same value as Row 3, Col. B |
Activated: Battery Voltage Not Activated: Same value as Row 3, Col. B |
Row 15 |
EQL |
Activated: Battery Voltage Not Activated: Same value as Row 3, Col. A |
Activated: Battery Voltage Not Activated: Same value as Row 3, Col. B |
Activated: Battery Voltage Not Activated: Same value as Row 3, Col. B |
Row 16 |
House Battery + |
Any voltage that is within the range of your batteries. |
Any voltage that is within the range of your batteries. |
Any voltage that is within the range of your batteries. |
Next Check the Alternator Wiring
Voltages Seem Consistently High or Low
If the temperature sensor is connected, you could be seeing the effect of the temperature compensation. If the voltage between house battery negative and the GROUND terminal on the regulator is more than a few millivolts (say 50 mv) then, there may be a problem with the
GROUND wire and/or connection.If the temperature sensor is connected, you could be seeing the effect of the temperature compensation. If the regulator just tripped to float, the batteries may be retaining a residual charge. Simply turn on a small load (about 10 amps such as the engine blower and cabin lights) and the regulator should start regulating.
Tachometer Drive Problems (Oscillates)
Some tachometers operate from a terminal on the alternator. The alternator signal is a half sine wave where its frequency is related to the engine RPM. The magnitude of the tachometer signal is dependent on the amount of current in the alternator field. Output current is also proportional to the field current, resulting in a conflict when field current needs to be low to regulate properly.
When the batteries are fully charged (especially gel batteries), little field current is necessary to maintain the float voltage at a proper level. Under these conditions, the regulator reduces field current to a level consistent with the output demand, so that the batteries will not be overcharged. The regulator is designed to be kind to the batteries first, and kind to the tachometer second. While special software in the regulator attempts to both regulate and still supply enough field current to keep the tachometer operating, the tachometer may still become erratic or even stop. This situation can be avoided by turning on a minimum load of a few Amps such as the running lights. This will load the alternator and result in more field current. (Be sure to turn off the load when it is no longer needed.)
At the end of the absorption cycle the alternator steps down to the float voltage over approximately 5 minutes. The tachometer may "pulse" at the time of the step about every 30 seconds. Do not be alarmed by this, as it is normal after the absorption stage. The minimum load mentioned above will alleviate any tachometer instabilities.
This can also happen when there is improper grounding of the alternator and/or wiring of the regulators
B+ and GROUND connections. Check that everything is physically wired as specified.