Introduction
The Energy Monitor/Controller 2001, EMON for short, is designed to completely monitor one house battery bank and one engine starter bank. It provides the resolution and accuracy necessary to eliminate battery discharge problems and its selectable alarms will keep you informed of abnormal conditions before they become dangerous.
The Energy Monitor is made in two versions: the H1, a one house bank unit with an auxiliary current sensing input and the H1A, a one house bank unit with an Alternator Current Sensor input. The H1 requires an option shunt to measure auxiliary current, while the H1A requires an optional Alternator Current Sensor to measure alternator current.
Alarms for abnormal conditions can be individually enabled or disabled, and the alarm setpoints can be programmed as desired. Alarm values and their activation controls are kept in non-volatile memory.
Interfaces are available to control external solar and wind generator relays, to start/stop a generator, and signal an external alarm circuit such as a horn or pager input.
A computer interface is provided to allow data gathering.
The Emon operates on 12 or 24 Volts, and input channels can be a mix of 12 and 24 Volts.
Measurements
The Emon measures voltage for two batteries, battery current, battery temperature, and either auxiliary current, (H1), or alternator current, (H1A). Note: Auxiliary current is measured with a shunt in the negative lead of the auxiliary charge source, while alternator current in measured in the positive lead. The auxiliary shunt can be used in the negative lead of an alternator that has a floating ground.
Full scale voltage is 39.99 Volts with a resolution of 0.01V. Battery current is measured to 399.9 Amps, with 0.1A resolution.
Auxiliary and alternator channels measure 199.9 Amps full scale with 0.1 Amp resolution. Full scale to 400 Amps can be accommodated on special order.
Voltage and Current Analog References
The Emon generates a voltage and current analog reference that can be used by an external charger to control the charge setpoint and the current limit. The voltage reference is temperature compensated. The voltage reference is 1/10 of the expected battery voltage for 12 Volt systems, and 1/20 for 24 Volts.
Note: Analog references are high impedance and must not be loaded with a resistance less than 100 Kohms.
Solar/Regulator Controller Signal
A digital signal is provided which interfaces to external solar/wind controllers and the Next Step or Smart Alternator Regulators. This signal instructs the controllers and regulators to stay in the absorption state until the battery is full. Note that the same signal is used from multiple solar/wind controllers as well as alternator regulators. It is a voltage signal that swings both positive, (asserted), and negative, (inactive). It must not be loaded with more than 0.003 Amps.
Activation setpoints for the control signal are programmable.
Generator Start/Stop Signal
A digital signal is provided which can be used to tell a generator to start or stop. The signal is asserted whenever battery capacity falls below a programmable setpoint, and it remains asserted until capacity is restored to a second programmable setpoint. For example the signal can be programmed to be asserted when capacity falls below 50% and stay asserted until capacity recovers to 90%.
The start/stop signal is pulled to ground with a small signal NPN transistor. An external relay may be required to interface it to a generator controller. No more than 0.050 Amps may be sunk by the transistor.
Alarm Signal
An external alarm signal is provided which is asserted whenever an abnormal condition is detected. Note: Abnormal condition setpoints are programmable, and alarms can be individually enabled or disabled.
The alarm signal is pulled to ground with a small signal NPN transistor. An external relay may be required to interface it to an external circuit. No more than 0.050 Amps may be sunk by the transistor.
Accuracy and Usability
The Energy Monitor can be very accurate and highly functional when it is installed and configured properly. Failure to configure the unit for your system particulars will not allow it to provide the accuracy and functionality expected. Accuracy is dependent on several parameters and conditions and an understanding of these is necessary before the performance of the unit is fully apparent.
Amp-hours remaining, percent remaining and the `gauge' messages are all based on the same arithmetic process. If one is not correct, then none will be correct. In subsequent paragraphs, the term Amp-hours remaining also means percent remaining and the gauge display.
Amp-hours remaining is dependent on the capacity, or `size' of the battery bank. Capacity is programmed under the Size ? prompt. For best result, don't accept manufacturer's claims of battery capacity ... many capacity claims are simply not true. For best accuracy, perform a capacity test. Capacity tests should be done once a year.
Amp-hours remaining is also dependent on Peukert's exponent. This value is programmed by the user. The only way that a valid exponent can be programmed is to first determine the exponent by two capacity tests.
When charging, Amp-hours depends on charge efficiency. During charge, an efficiency factor is arithmetically applied to charge current, reducing the actual current to its effective value. If charge efficiency is inaccurate, the state-of-charge information grows inaccurate with every charge.
Charge efficiency can be manually programmed by the user, or it can be calculated automatically. In most circumstances, the microcomputer can best determine recharge efficiency.
Before the microcomputer computes charge efficiency, three conditions must be met. First, the unit must be programmed to compute charge efficiency automatically. Secondly, the batteries must reach a full charge as defined by the FULL V and FULL I parameters. Finally, there must have been a prior discharge of the batteries of at least 50% of capacity. This discharge need not be the last discharge cycle ... it may have occurred at any time in the past since the last time a full charge occurred.
Periodically discharge below 50% and fully recharge. Without a periodic full charge, Amp-hours consumed and remaining continue to grow in error until the displays are meaningless. Be sure to periodically charge to the programmed full criteria, and periodically discharge below 50% of capacity.
The steps to accuracy are:
Once these steps have been understood and performed, the Energy Monitor will provide unequaled accuracy regarding battery state of charge.
Determining Peukert's Exponent
The Emon reports Amp-hours consumed as the product of Amps and time. Amp-hours consumed is not a good indicator or Amp-hours remaining because the faster the rate of discharge, the less total Amp-hours are available.
Back in 1897, a battery researcher by the name of Peukert published an equation that allows the calculation of available capacity at any discharge current. His equation, still valid today, states:
In Peukert's equation, C is a constant, namely the capacity of the battery. The letter I denotes the discharge current in Amps. The exponent n is related to battery construction, and is also a constant for any given battery. The letter t represents the time of discharge. Exponent n varies from more than one to about 2. Exponent n can be calculated by knowing the capacity obtained at any two discharge currents. That is, if we first discharge a battery at 5 Amps, and later at 20 Amps, and calculate the Ah obtained for each discharge, then the exponent n can be calculated from the equation below.
In the equation above,
is the hours of discharge at the current
. The second discharge is
and
.
The discharge procedure to determine the exponent is to first start with a fully charged battery. Discharge it at a convenient rate which is below your normal discharge rate, perhaps 5-8 Amps. When the voltage falls to 10.5 Volts, note the Amp-hours consumed and the length of time that the discharge took. Calculate the average Amps by dividing the Amp-hours consumed by the length of the discharge. For instance, assume that the discharge lasted for 49.5 hours and Amp-hours consumed was 300. Doing the division yields an average Amps of 6.06. This completes all the data needed for half of the above equation.
Charge the battery fully and repeat the discharge for the second data set. This time, however, discharge at a rate which is higher than your normal usage, perhaps that expected on an overnight passage. By making the discharge tests on either side of normal usage, you'll develop an exponent that is very accurate for the range which includes normal use. Once the two discharges have been done and Peukert's exponent calculated, program it into the Emon and enjoy the satisfaction of knowing Amp-hours remaining very accurately. The Emon is initialized at the factory with an exponent of 1.125. This is a convenient mid-range value. Large battery banks will have a lower exponent, while small banks will be higher. While this exponent may be close to your bank(s), we urge you to perform the discharge tests and be precise.
Interpreting Display Data
Data, which includes such elements as Battery 2 voltage, Amp-hours consumed and Battery 1 temperature are presented with a leading identifier, the value of the data, and a trailing identifier. The leading identifier describes what is being displayed, while the trailing identifier shows the units of the value.
For instance, a leading identifier of 1 with a trailing identifier of V means that the value is Battery 1 Volts.
Some of the displays, such as Life Amp-hours are too long to include the leading and trailing identifiers ...pressing the Menu key will show the prompt which identifies the data.
Operating the User Interface
The Emon is very easy to use after a short trial period. An eight character display and four keypads permit menu traversal, adjustment of setpoints, selection of options, and viewing of data.
All menus are circular with a varying number of prompts. By using the Up and Down keys, all menu prompts in a given circle can be seen. Prompts end in a question mark. When presented with a prompt, the Select key can be used to go to the menu or data display behind the prompt. You might think of the Select key as a Yes key to the questions asked by the prompt.
At any prompt, the Menu key can be used to escape to a higher menu. It is also used to abort data entry. You might think of the Menu key as an Escape key. It's the safest key to actuate when in doubt.
The top-most menu, which is presented whenever power is applied to the Emon, begins with the prompt Start ?. By actuating the Select key the next item in the top-most menu will appear.
Besides prompts, which are always terminated with a ? mark, there are data display, value adjustments, and option selections. The operations of the keypads have slightly different meanings depending on what is being displayed.
When viewing data, the Up or the Down key will move to the prompt for the preceding or next data display in the menu. As with prompts, the Menu key will escape to a higher level menu. The Select key merely refreshes the present data display, which is automatically updated once a second anyway.
Options are selected by using the Up and Down keys to set True, (Up), or False, (Down). The True or False refers to the question asked by the prompt. Once an option has been set to the desired state, the Select key is used to save the option in non-volatile memory. To escape changing an option, the Menu key can be used to exit the selection leaving the previously selected option in memory.
When an option is Selected, the next option in the menu is presented with its prompt.
Adjusting values uses the Up and Down keys to increment or decrement the displayed value. Holding the Up or Down key will make the increments or decrements greater the longer the key is held down. Once a value has been entered, the Select key will lock it into non-volatile memory. To escape setting a value, use the Menu key.
Sometimes when depressing a key for a long period to get a large change in the value, the display will fall behind and may display partial information or perhaps be blank. Releasing the key will allow the display to catch up.
Before reading the subsequent sections regarding menus, it's suggested to install and wire the Emon so that the keypad and display can be used.
Top-Most `Start' Menu
Start ? start by using the Select key
The Start menu is a menu of a single element. Pushing the Up or Down key just moves around this circular menu like all the rest of the menus. There isn't a higher level menu, so the Menu key has no where to go but to the Start menu.
Since the Menu key always escapes to a higher menu offering, pushing that key repeatedly will eventually reach the Start ? prompt. The Menu key doesn't set any values, so it's always safe to push the Menu key until the Start ? prompt is displayed.
Main Menu
Scroll ? sequentially shows data in the `scroll list'
View ? select data to be displayed
Program? set options, alarms, setpoint values
Reset ? clear accumlated Amp-hours and other data
Kwikeys? operate in four key `data' mode
The data that is presented when Scroll is active depends on the selections made under the Programming Menu. When scrolling, data is presented continuously. This is done with a descripter followed by a value. If you want to stop at a particular place, depress the Select key when the descripter is shown. The value for that descripter will then be continuously updated until the Select key is depressed to resume scrolling.
Selecting on the View ? prompt descends to the View Menu. Here you can choose the data to be displayed an item at a time.
Selecting on the Program ? prompt opens up the Program Menu where you can customize the operation of the Emon to suit your specific requirements.
Selecting on the Reset Menu enables you to clear accumulated data, such as Trip Amp-hours or Life Amp-hours. (A description of these is presented later.)
Selecting on the Kwikeys ? prompt drops you into an alternate use of the keypads. In the Kwikeys mode, the four keys are used to select a subset of the data available under the View Menu. The data behind the keys is:
Menu B1 Volts - Battery 1 is the house battery bank
Select B1 Amps - house battery current, minus is discharge
Up Amp-hours consumed from the house bank
Down B1 state-of-charge in English (3/4 Full)
Escaping the Kwikeys mode is done by actuating any one key five times in a row rapidly.
View Menu
The View Menu is used to select data to be displayed continuously until a different selection is made. Data to be viewed is grouped according to the source of the data ...that is house bank, starter bank, and auxiliary/alternator channel.
Choices under the View Menu are:
B1 data for B1, the house battery bank
B2 data for B2, the starter battery bank
Aux Ch/(Alt Ch) data for the auxiliary/alternator channel
View/B1 Menu
Under the B1 selection of the View Menu is all the measured and computed data for the house bank.
Gauge ? the state-of-charge in English, (3/4 Full)
Volts ? the present voltage on B1, the house bank
Amps ? the present current through B1, minus is discharge
Temp ? the present temperature of B1
Ah Con ? Amp-hours consumed since Full, minus is overcharge
Ah Rem ? Amp-hours remaining in the house bank
%Remain ? Ah remaining expressed as a percent of capacity
Time ? time remaining at present discharge rate
Trip Ah ? an Ah accumulator analogous to a trip odometer
Life Ah ? an Ah accumulator for long term acquisition
kWh ? kilo-Watt-hours used in the last discharge
kWh Tot ? a long term accumulation of kWh consumed
Effic the present recharge Amp-hour efficiency
T Size ? battery capacity adjusted for temperature
Note: The time remaining is based on the present discharge rate and present state-of-charge as well as a programmble parameter which represents the end point for the time calculation. See the `End %RM ?' prompt under programming. When the battery is not being discharged, the Time display shows `No Cons', for no consumption.
The Trip Ah is useful to measure the Ah consumption for specific events, say a weekend or week of use. Life Ah is best used to measure how many Amp-hours a set of batteries provided over their useful life.
View/B2 Menu
Volts the voltage of B2 the starter bank
View/Aux Ch/(Alt Ch) Menu
Amps the present current from the Aux/(Alt) device
Life Ah the accumulated Amp-hours from the Aux/(Alt) device
Program Menu
Charger modes and references for Ample Power chargers
Cntrlr modes and setpoints for solar/regulator and generator start/stop
B1 enable/disable alarms; setpoints; capacity; limits; values
B2 enable/disable alarms; alarm setpoints; calibrate
Aux Ch/(Alt Ch) calibrate
Back Lt operational mode, brightness, turn off delay
Contrst LCD contrast setpoint; when in doubt go Down
Scroll select data items for `scroll list'
Baud select Baud rate for computer interface
Fahren choose fahrenheit or celsius temperature display
Effauto choose automatic or manual charge efficiency
Program/Charger Menu
Under the Charger Menu, the operating mode and setpoint values can be selected which control the analog voltage and current references. These references can be used on the first generation Ample Power Smart Chargers, the Smart Alternator Regulator, V2, and the new Power Supply/Charger units. The Next Step Regulator and Smart Alternator Regulator, V3 do not use the analog references, but use a digital control signal instead.
Op Mode ? automatic multi-step or fixed setpoint operation
Values adjust the voltages for the various setpoints
Using the Op Mode Menu the references can be applied in a multi-step manner, or fixed at a particular setpoint. Selecting True for any given op-mode sets the others to False.
The Values Menu permits setting the voltages used for the various multi-step setpoints.
Program/Charger/Op Mode Menu
Auto automatic multi-step operation; recommended
Gas lock voltage to the `gas voltage' setpoint
Absorb lock voltage to the `absorption voltage' setpoint
Float lock voltage to the `float voltage' setpoint
Equaliz perform battery equalization
Program/Charger/Values Menu
Gas set the `gas voltage' setpoint
Absorb set the `absorption voltage' setpoint
Float set the `float voltage' setpoint
Equaliz set the `equalization' voltage
Amps adjust the Amps analog reference
Minutes set the maximum equalization minutes
Calibrt adjust voltage reference for charger
The Calibrt function is used to adjust the voltage reference so that battery voltage precisely matches the setpoint value. This is usually not necessary unless extreme accuracy is desired.
Program/Cntrlr Menu
B1 Full ? solar/regulator controller negates on `full' or voltage
Volt Lo ? connect voltage for solar/regulator controller
Volt Hi ? disconnect voltage for solar/regulator controller
Tmp Cmp ? True/False ...temperature compensate setpoints
SOC Lo ? generator Start state-of-charge setpoint
SOC Hi ? generator Stop state-of-charge setpoint
The controller signal is used for solar and wind generator control and also used with the Next Step and Smart Alternator Regulator, V3. The signal will be asserted when the voltage falls below the Volt Lo setpoint. If B1 Full is marked True, then the controller signal will be negated only when the batteries are full. Alternatively, the signal can be negated when the voltage exceeds the Volt Hi setpoint. This mode is selected by making B1 Full ? False.
Program/B1 Menu
The Program/B1 Menu is used to choose options and adjust setpoints for the house bank.
Alarm ? enable/disable alarms for B1
Volts ?calibrate full scale and zero for B1 voltage
Hi Alrm ? set the high voltage alarm setpoint
Lo Alrm ? set the low voltage alarm setpoint
Amps ?calibrate full scale and zero for B1 current
End %RM ? set the ending % remaining for time remaining calculation
B1C Lo ?set the % remaining for capacity low alarm
Hi Amps ? set the Amps value for the high Amps alarm
Tempcal ? calibrate the temperature sensor
Tmp Lim ? set the temperature for the high temperature alarm
Size ? enter the Amp-hour capacity at the 20 hour rate
Peukert ? enter Peukert's exponent for rate of discharge effects
Effic ? enter manual recharge efficiency
Full V ? set the voltage required to achieve a full condition
Full A ? set the Amps required to achieve a full condition
Full V and Full A settings are critical to proper operation. These parameters are used to detect when a full charge is achieved. For a full charge to occur, the battery voltage must be greater than the Full V setting, and the battery current must be less than the Full A setting.
The Full V setpoint should be set at slightly less than what the battery charger or alternator regulator delivers as a maximum. That is, 14.1 Volts is appropriate for a charger known to deliver 14.4 Volts.
The Full A setpoint should be set at about 5% of battery capacity in Amp-hours. That is, for 100 Ah of capacity, the Full A setpoint would be 5.0 Amps.
Failure to set Full V and Full A values appropropriately for the charge sources and the battery capacity will result is poor or meaningless Amp-hour computations.
An accurate Peukert's exponent is crucial to computing Amp-hours remaining, especially under high current loads. The book Wiring 12 Volts for Ample Power explains Peukert's exponent and how to derive it by two complete battery discharges.
Time remaining is calculated from the preset state-of-charge, using the present discharge current to the percent remaining set under the End %R ? prompt.
Program/B1/Alarm Menu
This menu is used to enable or disable individual alarms by setting them True, (enabled) or False, (disabled).
B1V Hi ? high voltage alarm for B1
B1V Lo ? low votage alarm for B1
B1T Hi ? high temperature alarm for B1
B1 50% ?alarm at 50% capacity for B1
B1 20% ? alarm at 20% capacity remaining for B1
B1C Lo ? alarm at programmable capacity setpoint for B1
B1 Full ? alarm when B1 reaches full
Hi Amps ? alarm if the high Amps setpoint is exceeded
Program/B1/Volts Menu
This menu permits calibration full scale and zero for the B1 voltage channel.
Zero ? adjust to read 0.0 with no input on B1V terminal
Calibrt ? calibrate full scale reading against known reference
Program/B1/Amps Menu
This menu permits calibration full scale and zero for the B1 current channel.
Zero ? adjust to read 0.0 with no input on B1 Amps terminals
Calibrt ? calibrate full scale reading against known reference
Program/B2 Menu
This menu is similiar to the B1 menu, but with fewer values to program. Refer to the prompts for B1 for an explanation of their meanings.
Program/Back Lt Menu
The Back Lt menu is used to control the LCD backlight intensity, and the mode of operation. The backlight can operate in the auto mode where it goes off when the keypad has been inactive for a prescribed delay time. In this mode the display will reactivate when any key is depressed. The backlight can also be on or off continuously. Since the backlight can take 4-6 times the energy draw of the Emon itself, operating in the auto mode is recommended.
Delay ? seconds to delay after last key activation before turning off
Bright ? controls backlight intensity
Op Mode ? select Auto or On/Off
Program/Back Lt/Op Mode Menu
Auto ? operate automatically if True; False let On/Off work
On ? if Auto is False, On=True means backlight on, False off
Program/Scroll Menu
This menu selects the data that will be displayed when the Emon is scrolling. A data element is put into the scroll list when it is marked True. Any element marked False is omitted.
B1 Volt ? battery 1 voltage measurement
B1 Amps ? battery 1 current measurement, minus for discharge
Time ? time remaining to the End %RM
B1 Temp ? battery 1 temperature
B1 Con ? battery 1 Amp-hours consumed
B1 Rem ? battery 1 Amp-hours remaining
B1 %RM battery 1 percent remaining relative to capacity
B1 Gaug ? battery 1 state-of-charge in English
B1 Trip ? Amp-hours accumulated in the Trip odometer
B2 Volt ? battery 2 voltage measurement
AX Amps ? Amps measured at the Aux/(Alt) channel
Program/Reset Menu
The Reset Menu is used to clear accumulators and restore settings to default conditions. All the resets except the Factory ? reset start and finish the reset action when the Select key is actuated.
Factory ? set all programmable parameters to factory defaults
B1 Trip ? clear the B1 Trip Ah accumulator
B1 Life ? clear the B1 Life Ah accumulator
B1 ? clear Trip and Life, and internal data, make full
kWh Tot ? clear the KwH total accumulator
Aux Ch ? clear the Life Ah counter
Cntrlr ? negate the solar/regulator signal and restart logic
Gen Set ? negate the generator Start/Stop signal and restart logic
Factory reset should only be done if a clean starting point to reconfigure is necessary. This will reset all the calibration constants along with all the other programmable values. Don't do a factory reset if you have special calibration constants set for the shunts.
By design, executing a factory reset is difficult. After Selecting on the prompt, the display shows three zeroes. The objective is to get 911 to replace the three zeroes. Actuate the Down key to get a 900 showing. Actuate Select to save that value and then actuate Up to get 910 showing. Now actuate Up again to show 911. Pressing the final Select will do the reset. You can always escape by pressing Menu at any time.
Mounting the Energy Monitor
The EMON II has been designed for the marine environment with the expectation that high humidity is normal and occasional splashes may be encountered. The main housing is packaged so that in theory, it is completely waterproof.
Signals exit the chassis via a waterproof cable and terminate on a free standing terminal block. Theory and practice are not always the same, so don't mount the unit where it will be repeatedly splashed or ever submerged. Often it is convenient to mount the unit in a companionway where it is readily available to persons at the helm and below. This is permissible if the companionway is normally protected with a dodger.
The display in the Emon has a fairly wide viewing angle, but don't mount it where it can only be seen at oblique angles.
Signal Names and Functions
NOTE: There are two terminal blocks with the Emon, TB1, and TB2. TB1 refers to the 16-pin terminal block and TB2 refers to the 6-pin terminal block.
Orient the terminal blocks so that Pin 1 is at the top.
Wiring Information
Use pre-tinned wire :: Over time, corrosion attacks even the
best connections. The use of pre-tinned wire will delay the onset of corrosion
and is worth the slight price differential.
Wire Size :: Wire gauge callouts on the drawings is only for
reference. Always consult a wire table to determine what size is appropriate
for your specific system. A wire table can be found in The Ample Power
Primer, which can be ordered from an Ample Power dealer, or downloaded from
the Ample Power website,
http://www.amplepower.com.
Wire Ground First :: Wire TB1-9, TB1-12, and TB1-16 first. Use
separate wires as shown on the diagram ...combining any of these wires may
reduce accuracy and stability.
Twist Temperature Sensor Wires :: Using a twisted pair for
temperature sensor wiring is recommended. Two wires can be twisted by chucking
one end of them in a drill motor and securing the other end of the wires.
Stretch thewires taut and operate the drill motor slowly.
Twisted, Shielded Pair :: Always use a twisted, shielded pair
for the shunt sense wires. Terminate the shield lead at the shunt.
Fuse at the Batteries :: Fuses are designed to prevent meltdown
of wiring. To be effective, they must be located close to the power, whether
that is battery positive, or positive distribution.
Prevent Chafe :: Avoid running wires near metal objects, if
possible. Always secure wires so that they cannot chafe with vibration.
Wiring Diagrams

Troubleshooting Information
Temperature versus Sensor Voltage ::
A faulty temperature sensor can produce erroneous readings for Amp-hours
remaining, and incorrectly compensate charger setpoints. Be sure to check the
temperature display when readings appear inconsistent. The temperaure probe is
designed to produce 2.98 Volts at
, (
). The sensor
voltage increases or decreases 0.01 Volts for every degree C change in
temperature.
Fuse Corrosion :: The voltage sense wires for B1 and B2 conduct very
low current. Without the backlight on, the power input wire also conducts quite
low current. The in-line fuses that connect these wires may corrode
sufficiently to disrupt circuit function. Visual inspection may not show much
corrosion.
Is the unit dead, or just the display? :: If the processor is
operating, then there will be voltage on TB1-1, representing 1/10th of the
expected charge voltage ...1.35 to 1.45 Volts. A higher or lower voltage
indicates that the processor is not operating.
Unit is dead :: If the unit is dead, and there is no voltage on
TB1-1, then there probably isn't power on TB1-11.
Be Prepared to Help Yourself :: Before contacting support, use a
voltmeter to take readings on all the pins of both TB1 and TB2. These readings
will enable support personnel to assist you.
Be able to describe the problem. The hardware and software for the Emon is complex, and there are many facets of its operation. Without specific details regarding the problem, support will not be able to help.
Field Replacement :: The cables that exit the Emon are sealed
with watertight bushings. These do not unplug. To replace a unit after
installation, remove the system wires from TB1 and TB2. Do not remove the wires
on these terminal blocks that go into the Emon housing.
Installation and Warranty Support
For questions regarding installation, operation, or warranty service contact PowerTap, Inc. who is the authorized warranty service agent for all Ample Power products. Their phone number is 206-789-4743, and their fax is 206-789-9003.
Email support is available from support@amplepower.com. See also the following
websites for more troubleshooting suggestions.