Mounting the Regulator
The regulator is protected against ambient humidity, but must be mounted
in a dry location free of moisture, dust, and other environmental
insults. The regulator will operate in temperatures to 60
C
(140
F).
Wiring Diagram
The wiring diagram above is the only way to wire the Smart
Regulator. Do not wire it in any other way, such as combining ground
wires or battery positive wires. For safety purposes, always use fuses where
shown.
NOTE: For those familiar with earlier regulators such as the SAR-V2 or Next
Step Regulators, note that all inputs and outputs on the SAR-V3 are active
on a positive signal. That means the PARALLEL solenoid, the
ERROR LAMP and the STATUS LAMP are wired to their
respective devices with the other end of the device returned to Negative
Distribution. All inputs at the terminal block are activated when they
are connected to battery voltage. Leave unused optional terminals
unconnected.
Signal Names and Functions
Battery voltage set-points are specified for
each voltage system, 12 or 24 volts, as 12 / 24 volts, respectively.
Status Indicator
The green Status Indicator and the external STATUS LAMP, if wired,
shows the charging state of the regulator. Status is shown by flashing the green
Status Indicator with On and Off times in seconds as shown in Table 1 below.
| Status | On | Off |
| ON/OFF Input Off | 3 | 3 |
| Bulk Charge | 2 | 1 |
| Gas Charge | 6 | 1 |
| Absorption Charge | 1 | 1 |
| Step to Float | 1 | 6 |
| Float Charge | 2 | 2 |
| Gas Lock | 3 | 1 |
| ABS Hold | 1 | 3 |
| Equalization Charge | 6 | 6 |
Error Indicator
The red Error Indicator and the external ERROR LAMP, if wired,
reports abnormal conditions. Errors are identified by On and Off times of
the red Error Indicator as shown in Table 2 below. They are listed in the
order that errors are displayed if there are multiple errors. All errors,
except the last one, attempt to shut off the field drivers until the error
condition subsides.
Note: The last error can also be a warning that voltage getting to the
regulator on the B
input is insufficient to fully drive
the field output.
| Error | On | Off |
| Voltage Runaway | 6 | 3 |
| Field Short Circuit | 3 | 6 |
| Bat. Volts disconnected | 3 | 1 |
| Can't turn field off | 1 | 1 |
| Bad Temperature Sensor | 6 | 6 |
| Over Temperature | 3 | 3 |
| Can't turn field on | 1 | 3 |
| Missing GROUND connection | 6 | 0.5 |
Voltage and Absorption Time Set-points
The voltage and the time of the absorption cycle are controlled by the internal
dip-switch, S1. Refer to Figure 2 for the location of S1. Select a charge
profile by setting the battery type switches on S1 according to the following
table.
| Battery Type | Sw 1 | Sw 2 | Sw 3 |
| Thick Plate Liquid | Off | Off | Off |
| Medium Plate Liquid | On | Off | Off |
| East Penn Gel | Off | On | Off |
| Concorde AGM | On | On | Off |
| Optima | Off | Off | On |
| Exide Gel | On | Off | On |
| Johnson Control Gel | Off | On | On |
| Ample Power Gel | On | On | On |
What You Should See
The regulator is on whenever power is present at B
. Without
voltage at the ON / OFF input, the regulator is simply controlling
the parallel solenoid, and will close the solenoid whenever the voltage on
BAT.VOLTS indicates that the main battery is being charged.
When the regulator is first turned on via B
, the red Error
Indicator will glow for 5 - 8 seconds before extinguishing. Then the green
Status Indicator will then start to flash the charge status.
If there is a positive voltage on the ON / OFF input, then the alternator should start to charge after the red Error Indicator goes off. Thus, alternator charging can be controlled via the ON / OFF input.
ABS Input
When battery voltage is applied to this input, the regulator is held at the
absorption set-point. Removal of the input signal causes the regulator to
begin stepping toward the float voltage. Step-to-float is an intermediate
mode where the float set-point is approached in small steps over time.
This is done in an attempt to maintain some alternator output and thus keep
the tachometer alive.
LOCK Input
This input locks the regulator at the gassing set-point, which is half-way
between the absorption and float set-points.
Removal of the signal toggles between stepping to float, or going to the absorption set-point. The first activation and then removal of the LOCK signal causes the regulator to step float. The next activation and then removal of the LOCK signal causes the regulator go to the absorption set-point, initializing the absorption timer. This cyclic behavior repeats. Thus, the LOCK input can be used to completely control the charge state at float, gas or absorption.
Input Priorities
The EQL signal overrides the LIMIT signal.
The EQL overrides the ABS
and LOCK signals.
On the current release, the LOCK signal overrides the
ABS signal. The LIMIT signal will limit current with
either LOCK or ABS.
Current Limiting
Two 20-turn potentiometers with two input signals permit duty cycle current
limiting at two independent set-points. Duty cycle current limiting is a mode
where the percentage-of-time that the regulator is driving the field is
set by the potentiometer. Current limiting is useful to reduce alternator
output, and thus reduce horsepower requirements from the engine.
Two settings are available. The control inputs are LIMIT, and EQL. Note that the EQL input serves a dual function depending on whether an internal jumper, P1, is in place. See the Equalization section for more information.
For normal limiting on a small engine, assert the LIMIT input. The EQL input can be connected to the same switch that enables another load on the engine. For example, a clutch driven pump may require a further reduction in current, so wire the EQL input to the switch that activates the clutch for the water pump. The potentiometer for LIMIT is R11. R12 sets the current limit for the EQL input. Refer to Figure 2 for R11 and R12 locations.
NOTE: The EQL input is used here as a second current limit set-point. See the following section below for information to do equalization.
Equalization
Equalization is a process where the voltage on the battery is allowed to rise
to a higher voltage, typically 16.2 / 32.4 Volts for most batteries, where the
applied current is limited to 3 - 7% of the Ah capacity of the
battery. The applied current must be set using R12.
The EQL input is used for a second current limit whenever the input signal is activated. To enter the actual equalization mode, the two pins of P1 must be first shorted with a jumper terminal or a switch connected to the two pins, refer to Figure 2. This changes the mode of the EQL input signal to regulate at the equalization voltage set-points as well as current limit. Then the EQL input should be momentarily activated for at least two seconds and then released. A second momentary action will terminate the equalization process. Equalization will terminate automatically whenever the ending voltage or time is achieved.
CAUTION: Equalization produces a higher voltage than some normal equipment can tolerate. Turn off equipment that will not tolerate an input of 17 / 34 Volts or more.
NOTE: The Smart Regulator does not permit equalization for the gel batteries but does permit equalization of absorbed glass matte batteries at an appropriate voltage.
Alternator Requirements
The alternator must be an externally regulated model with one
brush connected to ground and the other brush fitted with a
connection to make the field connection, (P-type).
NOTE: Alternators not rated for continuous operation
at high current and temperature may fail when driven by the
regulator unless current is limited to a safe value.
Troubleshooting
First, look at the Signal Names and Functions section above and
make sure that all required wires are in place and properly connected. We
have found that moving a wire such
as BAT.VOLTS or GROUND a few feet away from a good
Battery Positive or Negative Distribution could result in
undesirable regulation due to voltage spikes in the system.
To help diagnose voltage set-points, remove the T+ (RED)
connection to disable temperature compensation and prevent a faulty temperature
sensor from affecting the system.
NOTE: With temperature sensing, a higher battery temperature will result in
a lower battery voltage. Likewise, a lower battery temperature will
result in a higher battery voltage.
Second, if the problem still exists, obtain a copy of the SAR V3
Troubleshooting Guide which is available from the following sources:
Regulator Service Center
The troubleshooting guide was designed to help isolate a majority of the installation problems. Fill out the Troubleshooting Guide to determine if all measurements meet the specified requirements.
Finally, if you are unable to remedy the problem, contact the regulator service center with the SAR V3 Troubleshooting Guide completed for referencing.
Supplement: Using the SARV3 with Two Engines and Two Alternators Using the
Dual Alternator Controller
Ample Power products are manufactured by Ample Technology,
2442 NW Market St., #43, Seattle, WA 98107 - USA
Visit http://www.amplepower.com